The operator largely reads the machine's status from the panel in front of them. When the touched area triggers the wrong button, the screen goes dark, or the panel gets stuck on the startup logo, production stops even if the machine is otherwise sound. In applications for HMI repair in Beylikdüzü and surrounding workshops, the person who best describes the fault is often the operator who uses that panel every day. In this article, we address the symptoms observed by the operator one by one, explaining the possible causes behind each, and the careful ways to temporarily sustain production.

Touchscreen is drifting or unresponsive

If the operator presses a button and an adjacent button activates, or if a specific area of the screen is completely unresponsive, the problem lies with the touch layer. Possible causes include:

  • Calibration drift: Can be observed over time in resistive touch panels. If the panel's system menu has a calibration option, this is the first step to try.
  • Worn touch film: In frequently pressed areas, the resistive layer can wear, scratch, or bubble. Calibration will not fix this.
  • Bezel pressure: If the panel's mounting brackets are overtightened or the control panel cover is bent, the touchscreen might register constant pressure from the edges.
  • Contamination and liquid: Ingress of oil, coolant, or cleaning chemicals from the bezel edge can damage the touchscreen connection.
  • Touch controller fault: If the entire screen is unresponsive and the film appears intact, the problem might be on the board side.

Pressing with a pointed pen or screwdriver tip permanently punctures the touch film; it is important for operators to avoid this habit.

No display but the device is operating

If the screen is completely dark, yet the panel continues to communicate with the PLC, something happens on the machine when touched, or a very faint image can be discerned by looking closely at the screen with a flashlight, it is highly probable that the backlight is not working. In older panels, lighting is done with CCFL tubes; in newer ones, with LED strips. Possible causes include the tube reaching its end of life, a broken LED strip, or a fault in the inverter or driver circuit supplying the backlight.

This situation can be dangerous: an unwanted command might be issued if the operator touches the screen without seeing it. It is not recommended to continue operating the machine with a panel that has lost its display.

Lines, faded display, and color distortions

The appearance of horizontal or vertical lines on the screen, the disappearance of a part of the image, or color distortions are usually related to the LCD panel itself or the flexible cable and connector connecting it to the control board. If the lines change when the panel is lightly touched, the likelihood of a loose connection increases. A general fading of the image can be caused by aging of the backlight or a disturbed contrast setting. In panels exposed to heat for extended periods, spotting and darkening of the LCD may also be observed.

Keypad faults

In operator panels with physical buttons, a common complaint is a button not working at all, double-pressing, or acting as if it's constantly pressed. Possible causes in membrane keypads include conductive trace wear, tearing of the surface foil, and liquid ingress underneath. In some panels, the keypad is connected as a separate component; a loose connection cable can lead to all keys failing simultaneously.

Stuck on startup and rebooting

If the panel remains stuck on the startup screen when powered on, continuously reboots, or drops into the system menu without loading the project, the problem could be on the software side, in the memory, or related to the power supply. Possible causes:

  • Corrupted project file or an interrupted upload
  • Internal flash memory or memory card fault
  • Low supply voltage or aged capacitors in the panel's power circuit
  • Settings reset due to the panel's internal clock battery running out

The panel's power supply is among the first points to check. Low voltage in the 24 V DC supply line or a loose terminal can appear as a startup freeze. These measurements must be performed by competent electrical personnel and in compliance with safety regulations.

Communication loss

If the panel powers on, displays screens, but values are filled with invalid characters like "####" or a communication error message appears, the connection between the panel and the PLC has been lost. The cable, connector, communication port, IP address or address settings, and the port on the PLC side are possible sources. If the problem only occurs when the machine is operating, for example, when drives are engaged, the possibility of interference and shielding issues becomes prominent. If the communication port itself is faulty, the panel should be evaluated in the laboratory.

How does HMI repair proceed in the Beylikdüzü laboratory?

HMI repair is carried out in our laboratory in Beylikdüzü; the panel is not opened on-site. When the panel is brought to our laboratory in Mermerciler Industrial Estate or arrives by cargo, an acceptance record is made. During the diagnosis phase, the touch layer, LCD and backlight, power circuit, main board, and communication ports are evaluated separately. The scope and cost of repair are communicated in writing, work proceeds after customer approval, and the panel undergoes appropriate tests after repair. For the scope of our services, please review our HMI and operator panel repair page.

Project and screen software backup

The screens, alarms, and recipes on the operator panel are kept in a separate project file. Depending on the type of repair, especially for memory or main board operations, it cannot always be guaranteed that the project on the panel will be preserved. Therefore, it is important to back up the project while the panel is operational or can still be accessed, or to obtain the project file from the machine's installer or your own automation team. If you have the project file, please mention it in your application.

What to prepare when sending

  • Photo of the panel's back label (model, order code, serial number)
  • A short video or photo showing the fault
  • Operator's description: when it started, on which screen, with which action
  • Foam-padded and shock-resistant packaging to protect the screen surface

Temporarily sustaining production: points to consider

While the panel is under repair, some options can be considered to prevent production from stopping completely, but each requires caution:

  • Spare panel: If a spare panel of the same model and compatible firmware is available, it can be used by loading the correct project. Transferring a project to a different model may not always be possible and requires testing.
  • External mouse or keyboard: Some panels offer USB mouse support; a panel with a faulty touchscreen can be temporarily used this way. This option should only be considered if the display is clear.
  • Monitoring via computer: In some systems, the status can be monitored with a computer connected to the PLC; however, this is not a safe control interface for the operator.

Whichever option is chosen, it must be ensured that emergency stop and safety circuits operate independently of the panel, and any modification must be approved by the machine's responsible personnel.

Frequently asked questions

Should I assume the panel is completely broken when the screen goes dark?

Not always. If the panel continues to communicate with the PLC, the problem is usually with the backlight and is evaluated separately in the laboratory.

Can we perform touchscreen calibration ourselves?

If the panel's system menu has a calibration option, it can be tried. If the touch film is worn or cracked, calibration will not solve the problem.

Is it necessary to re-upload the project to a panel returning from repair?

This depends on the work performed. In operations involving the touchscreen or backlight, the project usually remains intact. If an operation related to memory or the main board was carried out, the project may need to be re-uploaded; this will be stated upon delivery. After the panel is installed on the machine, it is recommended to briefly check all screens, alarms, and recipe values with the operator, and verify PLC communication and date/time settings.

How can I find out what an error message means?

You can type the panel's label photo and the on-screen message into Fesbot. FS Otomasyon's free AI maintenance assistant shares the general meaning of the message and initial safe checks; it does not replace a definitive diagnosis.

If you have prepared your panel's symptoms and label information, you can apply using the service request form.

Related service

HMI and Operator Panel Repair

Report a Panel Fault
Service and contact

Let us find the right service for your device together.

Open a service request for a faulty device; for project needs, talk to our technical team. Our Beylikdüzü, Istanbul laboratory accepts devices from all over Türkiye.

FS Otomasyon building at sunset
WhatsAppSend photos and device details Phone+90 545 729 49 11
Photo